The ChloriDos™ Advance system accurately generates, doses and monitors Chlorine Dioxide into water services. It is used to disinfect water and control legionella and other potentially harmful pathogens. ChloriDos™ technology generates in situ, within a safe, self contained reactor unit, Chlorine Dioxide concentrates between 1% and 5% either by acid/ chlorite method or stabilised Chlorine Dioxide pre cursor and activator. The Chlorine Dioxide solution is then further diluted into a motive water stream and injected into the process on site. Installations are typically either recirculating a water storage tank or rising main.

ChloriDos™ Advance

 

Chlorine Dioxide Generation, Dosing and Monitoring

General Technical Data

  • Conex Dia 1 analyser/controller
  • Aquacell with hydro mechanical cleaning
  • Measuring range 0-10mg/l ClO2
  • Analogue or digital water meter inputs
  • Water meter overdose protection
  • Unique Boost feature to maintain disinfection levels during low flow periods
  • Volt free outputs for connection to BMS systems
  • Internal contactor for 0.37kW circulation pump (pump optional)
  • Safety flow sensors in sample and dilution flows
  • Sight glass for visual ClO2 indication
  • Max operating pressure 8 Bar (sample cell 3 Bar)
  • Enclosed reactor with flush facility
  • Remote alarm terminals
  • 4-20mA scalable analogue outputs for ClO2 and temperature
  • Superior build quality for trouble free operation

 

All ChloriDos™ systems are supplied fully wet/pressure tested to 6 Bar (ClO2 reaction vessels 15 Bar), with fully configured control software, completed operational diagnostic checks, unique ID serial numbers and full documentation.

 

ChloriDos™ Model Product Description Typical ClO2
production g/h
CDS-AD2E-120-300 ChloriDos Advance System (electronic pumps) 2 - 300 g/h
CDS-AD2E-240-600 ChloriDos Advance System (electronic pumps) 5 - 600 g/h
CDS-AD2D-100-250 ChloriDos Advance System (digital pumps) 2 - 250 g/h
CDS-AD2D-220-550 ChloriDos Advance System (digital pumps) 5 - 550 g/h

 

Download

ChloriDos™ Advance - PDF Data SheetChloriDos™ Advance - PDF Data Sheet

Conex Technical Data
Electronics 16 bit microprocessor system
Display High resolution plain text LCD with back light
Relay Outputs 1 alarm relay
2 controller relays (230V ,6A, max 550VA)
Signal Outputs 4 analogue (4-20mA) outputs galvanically isolated from the inputs, max load 500 Ohm
Temperature compensation Manually or automatically from temperature sensor (fitted)
Calibration With plausibility check
Admissable temperature Operationa 0 - 50°C
Storage -22 to 65°C
Relative Air Humidity Max 90% at 40°C (not condensing)
Limit Values Adjustable to physical variable within measuring range
Hysteresis 0 to 50% of the upper limit of the measuring range
Set Point selection 0 to 100% of measuring range
Proportional Band (Xp) 0.1 to 3000%
Reset time (Tn) 1 to 3000s resolution 1s
Deriv action time (Tv) 1 to 3000s resolution 1s
On time 0.1 to 10s
Constant load 0 to 50%

 

ChloriDos™ Technical Data
Description Code
Mains supply 230V ±10% 50Hz 30mA
RCBO protection recommended (6A)
Power Consumption 450 W
Aux Power Rated 2A at 230V
General alarm output Rated 6A at 230V
(resistive)
Water meter input Digital or analogue (4-20mA)
Optional circulation pump Recommended Grundfos CHN2-20 or alternative pump max 0.37kW
Max operating pressure 6 Bar
Pipe connections 1/2 " PVC unions
Dosing concentration 2 - 5%
Environmental protection
level
IP65
Back board dimensions 976 x 1100mm
Water meter input Digital or analogue (4-20mA)
Terrain dimensions 1200 x 1600 x 650mm
Weight Back board 45kg approx
Terrain 195kg approx

ChloriDos™ Housing